Add to Cart
lead acid rechargeable battery 12v 55ah Sealed AGM battery for Scooter/UPS
> Product Features
1. Good discharge performance
2. Low self-discharge rate:≤3%/month
3. High sealed reaction efficiency≥99%
4. Wide operation temperature:﹣20℃~60℃
5. Tight assembly,low internal resistance
6. Wiring terminals: 2 or more types of wiring terminals, multiple choices
7. Diaphragm: improved AGM diaphragm makes the resistance lower, high assembly pressure increases the service life of deep circulation
8. Shell: high strength ABS (ul94-hb); Ul94-vo optional
9. Terminal sealing: (mechanical + epoxy resin glue) double sealing
Products are widely used in hybrid wind off-grid power station, household energy storage power generation system, monitoring system,equipment, street lamp, outdoors, electric cars, electric sightseeing cars, street cleaner, sanitation trucks, the uninterrupted power source(UPS), communication base station, and emergency EPS system, etc.
Battery Model No. | FBR12-55 | |
Nominal Voltage | 12V | |
Capacity | 20HR(10.8V) | 55Ah |
(25ºC) | 10HR(10.5V) | 48.4Ah |
1HR(9.6V) | 34Ah | |
Dimension | Length | 230±2mm |
Width | 140±2mm | |
Height | 211±2mm | |
Total height | 215±2mm | |
Approx. Weight | 16.5kg±5% | |
Terminal type | F14 | |
Internal resistance(Fully charged,25ºC) | Approx 7mΩ | |
Capacity affected by | 40ºC | 102% |
Temperature(20HR) | 25ºC | 100% |
0ºC | 85% | |
-15ºC | 65% | |
Self-discharge(25ºC) | 3month | Remaining Capacity:91% |
6month | Remaining Capacity:82% | |
12month | Remaining Capacity:65% | |
Nominal operating temperature | 25ºC±3ºC(77ºF±5ºF) | |
Operating | Discharge | -15ºC-50ºC(5ºF-122ºF) |
temperature range | Charge | -10ºC-50ºC(14ºF-122ºF) |
Storage | -20ºC-50ºC(-4ºF-122ºF) | |
Float charging voltage (25ºC) | 13.5 to 13.8V Temperature compensation:-18mV/ºC | |
Cyclic charging voltage (25ºC) | 14.5 to 15V Temperature compensation:-30mV/ºC | |
Max charging current | 16.5A | |
Max discharging current | 550A(5sec.) | |
Designed floating life(20ºC) | 10years |
Component | Positive plate | Negative plate | Container | Cover | Separator | Electrolyte | Safety valve | Terminal |
Raw material | Lead dioxide | Lead | ABS | ABS | AGM | Sulfuric acid | Rubber | Copper |
F.V/Time | 10min | 15min | 30min | 60min | 2h | 3h | 4h | 5h | 8h | 10h | 20h |
9.6V | 262 | 202 | 121 | 74.2 | 43.8 | 31.2 | 25.2 | 21.5 | 14.8 | 12.2 | 6.47 |
9.9V | 254 | 197 | 118 | 73 | 43.6 | 31 | 25.1 | 21.4 | 14.7 | 12.2 | 6.46 |
10.2V | 243 | 190 | 115 | 71.2 | 43.2 | 30.8 | 24.9 | 21.3 | 14.6 | 12.2 | 6.44 |
10.5V | 233 | 183 | 112 | 69.7 | 42.6 | 30.6 | 24.7 | 21.1 | 14.5 | 12.1 | 6.4 |
10.8V | 220 | 173 | 108 | 67.6 | 41.5 | 29.7 | 24 | 20.5 | 14.1 | 12 | 6.36 |
>Constant Power Discharge Characteristics(Watt,25ºC)
F.V/Time | 10min | 15min | 30min | 60min | 2h | 3h | 4h | 5h | 8h | 10h | 20h |
9.60V | 2825 | 2214 | 1353 | 845 | 508 | 367 | 297 | 255 | 176 | 146 | 77.7 |
9.90V | 2741 | 2160 | 1326 | 833 | 505 | 365 | 295 | 253 | 175 | 146 | 77.5 |
10.2V | 2628 | 2081 | 1285 | 812 | 500 | 362 | 293 | 251 | 174 | 145 | 77.3 |
10.5V | 2514 | 2010 | 1254 | 795 | 493 | 360 | 291 | 250 | 172 | 144 | 76.9 |
10.8V | 2373 | 1904 | 1208 | 770 | 480 | 349 | 282 | 242 | 167 | 143 | 76.3 |
Float charge
The floating charge voltage should remain constant
The effects of too high or too low a floating charge voltage is as follows:
Too high for extended period (overcharge): it may shorten battery life
Too low for extended period (undercharge): it may not meet load or cause variances in battery voltage that will decrease the capacity of battery pack and shorten their life.
Recovery charge
When resuming charging, the initial current should be limited to 0.1C-0.3CA
Temperature compensation
When the temperature deviates from 25℃, please modify the voltage as 3mv/cell fo every 1C deviation.
The equalizing charge
The equalizing charge voltage is 2.30 - 2.35V/cell.
Cautions during charge
(a)If the charge current exceeds 0.05CA at the final stage of charge, the storage batter may be permanently damaged in appearance and life. Pay special.attention to charging voltage.
(b)The battery charger should be the one that can provide automatic constant voltage with drooping characteristics, if other types will be used, please contact us before applied.
1. When you wish to store the battery, battery should be stored without charger and load at dry location with low temperature.
2. If batteries are stored for a long period, give a supplementary charge before use.